//Fire Suppression System (Clean Agent)
Server & Electrical RiskNFPA 2001 / IS:15493

Fire Suppression System (Clean Agent)

FM-200, Novec 1230, and CO2-based clean agent suppression systems that extinguish fires within seconds without leaving residue or damaging sensitive equipment. Ideal for areas where water-based systems would cause more harm than the fire itself.

Discharge Time

< 10 seconds (FM-200 / Novec)

Design Concentration

7–9% FM-200 / 5.8–8% Novec

Residue

Zero — safe for electronics

WhatsApp
MSME Registered Free Site Visit Installation + AMC
Fire Suppression System (Clean Agent)

Fire Suppression System (Clean Agent)

NFPA 2001 / IS:15493

Certified

Working Principle

How It Works

A network of detector heads continuously monitors the protected enclosure. On detection, the system enters a pre-discharge countdown (typically 30–60 seconds for occupant evacuation), then releases gaseous agent from pressurised cylinders through ceiling nozzles to flood the room uniformly. FM-200 and Novec 1230 extinguish fire by heat absorption; CO₂ extinguishes by oxygen displacement. The agent disperses without leaving any residue or moisture, fully protecting sensitive electronics and documents.

Product Range

Available Types & Variants

FM-200 (HFC-227ea) — occupied spaces
Novec 1230 (FK-5-1-12) — low GWP
CO₂ Total Flooding — high-hazard (unoccupied)
Inert Gas (IG-541 / IG-55)
Pre-Engineered Self-Contained Unit
Modular Multi-Cylinder System

What You Get

Key Features

FM-200 / Novec 1230 / CO2 gas-based agents
Discharges within 10 seconds — no residue or water damage
Automatic detection-linked release with manual override
Safe for occupied spaces (Novec 1230 / FM-200)
Complete design, installation & cylinder refilling support

Use Cases

Where It's Used

Server Rooms
Data Centres
Electrical Panel Rooms
Control Rooms
Record Rooms

At a Glance

Technical Specifications

Discharge Time

< 10 seconds (FM-200 / Novec)

Design Concentration

7–9% FM-200 / 5.8–8% Novec

Residue

Zero — safe for electronics

NOAEL (Safety)

9% FM-200 / 10% Novec 1230

Certification

NFPA 2001 / IS:15493

Keep It Ready

Maintenance & AMC Tips

1

6-Monthly weight check of all cylinders (tolerance ±5%)

2

Annual inspection of nozzles, pipework, and enclosure integrity

3

Test detection and control panel with simulated alarm annually

4

Verify room enclosure integrity (gas retention test) every 5 years

5

Service automatic door releases and abort switches annually

Legal & Compliance Requirement

Server rooms, UPS rooms, control panels, and data centres cannot be protected by water or dry powder systems without destroying the very equipment being protected. NFPA 2001, IS:15493, and insurance underwriting standards for IT and data infrastructure require clean agent suppression as the only approved solution for these environments.